Repairs to Laboratory Air Conditioning North Wales

Location

North Wales

Date

October 2024

Value Range

Under £750

Product Category

Service & Repairs

See more case studies

Repairs to Laboratory Air Conditioning System

Deep Clean of Wall Mounted Air Conditioning System

Read More

Pharmaceutical Walk-In Chillstore

Design, supply & installation of Walk In Pharmaceutical Chillstore with an operating range of 2°C to 8°C.

Read More

Deep Clean of a Wall Mounted Air Conditioning System

Deep Clean of Wall Mounted Air Conditioning System

Read More

Large Refrigeration & Air Conditioning Project for Pharmaceutical Manufacturer

Design, supply & installation of multiple Walk In Pharmaceutical Chillstores, each with an operating range of 2°C to 8°C.

Read More

ICE maintenance contract extends warranty on new equipment for up to 10 years

ICE Ltd the experts in Refrigeration & Air Conditioning, provide a case study of how a maintenance contract extends warranty of new equipment for up to 10 years.

Read More

Design & Build of Walk-In Chillstore

Design, supply & installation of Walk In Pharmaceutical Chillstore with an operating range of 2°C to 8°C.

Read More

ICE were tasked with carrying out a deep clean of an air conditioning cassette system over a weekend, when the Laboratory was out of use.

The system was leaking water due to a failed condensate pump caused by a blocked drain hose, following the repair it was recommended that the system was stripped down and deep cleaned to prevent further pumps from failing.

Scope of work

Strip down and deep clean a cassette unit and drains within the laboratory area over a weekend.

How ICE helped

Air Conditioning North Wales Repair – The work was assigned to our Senior Service Engineer Harry James for continuity as it was he who attended the original service call.

The first step in the process was to electrically isolate the unit and strip it down. This involved removing the casings, filters, and fan impellor. Once this was done, the indoor evaporator coil was exposed and sprayed with Easycare evaporator cleaner from Advanced engineering, along with the fan impellor and filters.

After 10 minutes, the cleaner was rinsed off using a jetwash. Next, the casings were cleaned with disinfectant and polished with case cleaner.

The drain hose was blown out using gallo gun cartridges to remove any potential build up within the drain.

The unit was then reassembled and sprayed with OdourGuard to provide protection from odours and unpleasant smells. We take pride in ensuring that our work not only resolves the issue at hand but also leaves the customers unit looking and smelling as good as new.

Finally, the system was recommissioned and left working.

Results

Air Conditioning North Wales Repair – The repair we carried out will prevent the drain hose from re-blocking, allowing the newly fitted condensate pump to remove water effectively. Additionally, we left the system clean and free from bacteria and fungi, resulting in significantly improved airflow and increased efficiency.

We are ready to help with your air conditioning, refrigeration and ventilation enquiries.

If you have an enquiry, please complete the contact form and our team will be in touch. We look forward to hearing from you and look forward to building a winning partnership

Get in touch today!

    By sending this message, you agree to the Terms of use and Privacy Policy.

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.